FBE-ESP-FIREBEAM-XTRA User Guide
NSW 02 9644 7144 QLD 07 3252 5366 VIC 03 9544 2211 WA 08 9349 2972 FIREbeam Xtra User Manual 14 2-3-0-2700/ISS2/21.OCT19 Screen and Menu Systems Home Screen NORMAL This is the screen you would normally see when the beam is commissioned. FIRE The air quality level has fallen below the fire threshold setting. If alarm is set to latching and you need to reset from fire press enter to see this screen and press enter again to reset and return to the normal screen. This can also be reset by dropping the power to the beam for 5 seconds. If set to auto reset, it will reset to normal automatically. See the menu system on the following pages on how to change between auto and latching if required. FAULT The beam path has been fully blocked within 1 second (used when fault testing in commissioning. ERROR No communication with the controller. This could be that the flying lead is not connected, or that the head is not connected to the controller. This can be checked by reading the resistance across the black and grey terminals, if connected it should read 110 ohms, if not connected at one end this will read 220 ohms. ALIGN This screen will appear when the beam is performing a self-alignment, normally because of building movement. DIRT COMP This is due to the compensation for dirt build up reaching its maximum - FAULT or FIRE LED may be flashing.