FBE-ESP-FIREBEAM-XTRA User Guide
NSW 02 9644 7144 QLD 07 3252 5366 VIC 03 9544 2211 WA 08 9349 2972 FIREbeam Xtra User Manual 2-3-0-2700/ISS2/ 1.OCT19 21 Technical Specifications Electrical Specifications Supply Voltage 17 to 41 VDC Supply Current 3.5 mA (constant current) in all operational states Constant Current 17 mA (constant current) in fast commissioning Environmental Specifications Temperature -10 °C to +55 °C Humidity 10 to 95% RH Non-condensing Ingress Protection Index IP65 when suitably mounted and terminated Mechanical Specifications Beam Head 180 mmH x 155 mmW x137 mmD, Weight 1.1Kg Controller 185 mmH x 120 mmW x 62 mmD, Weight 0.55g 70KIT140 Mid-Range Reflector 293 mmH x 293 mmW x 5 mmD, Weight 0.8Kg 140KIT160 Long Range Reflector 394 mmH x 394 mmW x 5 mmD, Weight 1.8Kg Adapter (mounts the Beam Head onto unistrut) 270 mmH x 250 mmW x 5 mmD, Weight 0.6g Optical Specifications Optical Wavelength 870 nm Maximum Angular Alignment ±5° Maximum Angular Misalignment Beam Head ±0.4°, Reflector ±2° (static not auto-aligning) Operational Specifications Protection Range FIREbeam XTRA Standard Product 7 to 70 metres (use short range mask for distances between 7 & 20 metres)