NSW 02 9644 7144 QLD 07 3252 5366 VIC 03 9544 2211 WA 08 9349 2972 FIREbeam Xtra User Manual 2-3-0-2700/ISS2/21.OCT19 5 Note: The standard FIREbeam Xtra and range kits can be supplied as anti-fog sets as a special order. Installing, Commissioning and Testing Step 1 - Mounting the Head Screw the head backing plate to the wall - always try to use as sturdy a location as possible, such as brick or major structural steels (avoid mounting to outer metal cladding etc). Avoid mounting the head where direct sunlight can shine directly into the ‘eyes’ of the beam (care should be taken when mounting in glass atriums). Ambient sunlight will not affect the beam. Also available - Unistrut adapter plate Use this accessory for easy mounting to Unistrut fabrication. Holes are pre-drilled to the correct pitch of the head and conveniently positioned for use with Unistrut. A C B D A 2 knock-outs are provided on both sides. Take care when using drills not to damage the circuit board. Only punch out with head open and disconnected from power. B Wire to low level controller using bottom colour coded terminals. C Wire into system as required (see “Wiring Configuration” on page 7). Ensure that all wiring is below the level of the front edge of the box. D Screw in through holes provided outside of the rubber seal.