FBE-ESP-FIREBEAM-XTRA User Guide

NSW 02 9644 7144 QLD 07 3252 5366 VIC 03 9544 2211 WA 08 9349 2972 FIREbeam Xtra User Manual 6 2-3-0-2700/ISS2/21.OCT19 Connect the head to the base plate by first plugging in the connector. Do not force in, white wires should be uppermost. Should you forget to connect this the controller screen will read ERROR. To avoid damaging the detector head never dangle the front cover assembly from the ribbon cable. IMPORTANT ensure the connector is this way up. Screw the head screws down with the 3mm allen key provided. Your wiring should be flush and not flattened by tightening down screws. Step 2 – Mounting the Controller Important mount the controller at eye level and ensure easy access. Screw in through holes provided outside of the rubber seal. Wire to head using colour coded terminals. If this connection is not made, “ERROR” will appear on the controller, this connection can be checked by reading the resistance across the black and grey terminals, they will read 110 ohms if OK or 220 ohms if not connected properly.

RkJQdWJsaXNoZXIy OTk5NjE4