FBE-ESP-FIREBEAM-XTRA User Guide

NSW 02 9644 7144 QLD 07 3252 5366 VIC 03 9544 2211 WA 08 9349 2972 FIREbeam Xtra User Manual 2-3-0-2700/ISS2/21.OCT19 7 Wiring Configuration The output current of the internal control module will need to be set at 22 mA. The output will also need to be programmed so that it is powered in its normal state. On a control panel reset the output will need to change state for a minimum period of 5 seconds. NOTE: You should consult the relevant control panel documentation on how to program this functionality. Step 3 – Programming the Analogue Address The FIREbeam Xtra is programmed via the integral Control Module situated on the main PCB within the head unit. To program an address, you will require a TCH-B200 Hand Held Programmer and a PL-3 Programming Lead (both provided separately). Connect the PL-3 Programming Lead to the TCH-B200 Hand Held Programmer and then to the blue programming socket on the FIREbeam Xtra Control Module. Refer to the TCH- B200 Instructions for further details on programming addresses. The programmed address can be written on the module label in the space provided.