FBE-ESP-FIREBEAM-XTRA User Guide
NSW 02 9644 7144 QLD 07 3252 5366 VIC 03 9544 2211 WA 08 9349 2972 FIREbeam Xtra User Manual 10 2-3-0-2700/ISS2/21.OCT19 More power will be output than is necessary to cover the distance and these levels will then be reduced once the auto align process takes place. The air quality figure at this point should normally stay at 0%. Pre-Align Complete will now be indicated. Press enter to accept Pre-Alignment and confirm these settings by pressing the right key and enter into Manual Alignment. The FIREbeam Xtra is looking for the far wall of the building and in some shorter distance applications will stop raising the IR Power when it’s sufficient for the distance. In these cases, you can press Enter to accept the Pre-Alignment then the right key and enter into Manual Alignment. CAUTION: If you have not allowed the 50cm radius and the beam encounters an obstruction this will also stop raising the IR Power and halt the Pre-Alignment as the beam will assume it has found the far wall. You will need to identify and move the obstruction or reconsider the positioning of the beam. You can identify that the beam is obstructed if the right-hand figure (Air Quality) has risen and is fluctuating between 5%-10%. Obstructions near the head will disturb the pre-alignment process and care should be taken to ensure no solid objects are close to the beam path.