NSW 02 9644 7144 QLD 07 3252 5366 VIC 03 9544 2211 WA 08 9349 2972 FIREbeam Xtra User Manual 12 2-3-0-2700/ISS2/21.OCT19 The beam can be moved on both X and Y axis to a maximum 5 degrees using the left (x-), right (x+), up (y+) and down (y-) keys. Looking at the reflector this will move the beam across the reflector as shown: Holding the keys down will quickly scroll through to your desired position, on release of the button the screen will revert to the actual beam position and can be seen stepping toward the requested position. To confirm the beam is seeing the reflector, cover the reflector as this should drop the AQ and therefore prove the beam is on the reflector. In the example above moving the y axis down (y-) results in a greater AQ Try and achieve as high an AQ as possible, it must be at least 80 to 100% ideally above 100%. Once you have achieved this you can move onto Auto Alignment. Stage Four - Auto-Alignment Having received an AQ reading of over 100% in manual mode press enter to exit manual and enter again to go into auto alignment mode. Auto Alignment is an automatic process that will firstly reduce the RX Sense and IR Power to accommodate the best settings for beams environment. The beam will automatically align to the centre of the Reflector, you will notice the X and Y axis moving as beam moves up, down, left and right to find the centre point. When finished beam will state Align Complete and pressing Enter to confirm will show Air Quality 100% Status Normal.